DEC REQUEST DS 2018-051 STAFF ANALYSIS

 

ISSUE: DS 2018-051. Petitioner seeks a Declaratory Statement on an interpretation of Chapter 2 Scoping Requirements, Section 201.1 Scope, Section 201.1.1 Vertical accessibility, Section 206.2.3 Multi-Story Buildings and Facilities, of the Florida Building Code 6th Edition (2017) Accessibility.

Petitioner seeks clarification of the following question:

 

Does the Florida Accessibility Code - Sections 201.1.1 and 206.2.3 allow Limited­ Use / Limited Application Elevators or Platform Lifts installed per FAC 408 or 410 to meet the requirements for vertical accessibility in buildings where the ADA does not require vertical accessibility?

             

 

Situation/Background:

 

Petitioner is Clark M. Stranahan of C4 Architecture request a declaratory statement from the Florida Building Commission for the future two-story Office building in Seminole County, Florida (see Appendix A). The statement is in regard to the requirement to use an elevator for vertical accessibility in lieu of a Limited-Use/ Limited Application Elevator or Platform Lift to achieve vertical accessibility as required by FAC 201.1.1.

It is our opinion that the intent of the Florida Accessibility Code is to allow a Limited-Use/ Limited Application Elevator installed per FAC 408 or a Platform Lift · installed per FAC 410 in buildings where the ADA would not otherwise require vertical accessibility for the following reasons:

The ADA does not require two story buildings that are not a shopping center, shopping mall or the professional office of a medical provider to have vertical accessibility. FAC Advisory 201.1 Scope states, "Where the ADA Standards do not require an accessible route to each and every level, the Florida requirement may be waived down to the requirement of the ADA Standards." See Appendix B.  Advisory.”

Section 206.2.3 also suggests that the Florida requirements may be waived. "Note: the following advisories on the Exceptions to 206.2.3 are provided for consideration when waiving Florida Vertical Accessibility requirements down to ADA Standards". The advisories that follow reference the exceptions in 206.2.3 that are shown as "Reserved." See Appendix C.

In previous versions of the code, this issue was clear. The 2007 Florida Building Code 11-4.1.3 Exception #1 states "Elevators are not required in facilities that are less than three stories or that have less than 3,000 square feet per story unless the building is a shopping center, a shopping mall, or the professional office of a healthcare provider, or another type of facility as determined by the U.S. Attorney General." See Appendix D.”

 

Florida Building Code 6th Edition (2017) Accessibility

 

CHAPTER 2: SCOPING REQUIREMENTS

SECTION 201APPLICATION 

201.1Scope.

This code establishes standards for accessibility to places of public accommodation and commercial facilities by individuals with disabilities. This code shall also apply: to state and local government facilities pursuant to Section 553.503, F.S.; to private clubs pursuant to Section 553.505, F.S.; and to residential buildings pursuant to Section 553.504(2), F.S., and the ADA Standards for Accessible Design. All new or altered public buildings and facilitiesprivate buildings and facilitiesplaces of public accommodation and commercial facilities subject to this code shall comply with this code.

This code applies to: All areas of newly designed and newly constructed buildings and facilities as determined by the ADA Standards for Accessible Design; portions of altered buildings and facilities as determined by the ADA Standards for Accessible Design; a building or facility that is being converted from residential to nonresidential or mixed use as defined by the Florida Building Code where such building or facility must, at a minimum, comply with s. 553.508, F.S., and the requirements for alterations as determined by the ADA Standards for Accessible Design; buildings and facilities where the original construction or any former alteration or renovation was carried out in violation of applicable permitting law.

201.1.1Vertical accessibility.

Sections 553.501-553.513, F.S., and the ADA Standards for Accessible Design do not relieve the owner of any building, structure or facility governed by those sections from the duty to provide vertical accessibility to all levels above and below the occupiable grade level regardless of whether the Standards require an elevator to be installed in such building, structure or facility, except for:

(1)Elevator pits, elevator penthouses, mechanical rooms, piping or equipment catwalks and automobile lubrication and maintenance pits and platforms.

(2)Unoccupiable spaces, such as rooms, enclosed spaces and storage spaces that are not designed for human occupancy, for public accommodations or for work areas.

(3)Occupiable spaces and rooms that are not open to the public and that house no more than five persons, including, but not limited to equipment control rooms and projection booths.

(4)Theaters, concert halls, and stadiums, or other large assembly areas that have stadium-style seating or tiered seating if sections 221 and 802 are met.

(5)All play and recreation areas if the requirements of chapter 10 are met.

(6)All employee areas as exempted by 203.9.

(7)Facilitiessites and spaces exempted by section 203.

Buildings, structures and facilities must, at a minimum, comply with the requirements of the ADA Standards for Accessible Design.

Advisory 201.1 Scope. These requirements are to be applied to all areas of a facility unless exempted, or where scoping limits the number of multiple elements required to be accessible. For example, not all medical care patient rooms are required to be accessible; those that are not required to be accessible are not required to comply with these requirements. However, common use and public use spaces such as recovery rooms, examination rooms, and cafeterias are not exempt from these requirements and must be accessible.

Florida vertical accessibility requires all levels in all new buildings, structures and facilities and all altered areas of existing buildings, structures and facilities to be accessible to persons with disabilities. All new and altered areas must comply with the ADA Standards for Accessible Design including requirements for accessible routes. Where the ADA Standards do not require an accessible route to each and every level, the Florida requirement may be waived down to the requirement of the ADA Standards.

 

206.2.3Multi-Story Buildings and Facilities.

At least one accessible route shall connect each story and mezzanine in multi-story buildings and facilities.

Notwithstanding the requirements and exceptions of this section, section 201.1.1 shall apply.

EXCEPTIONS:

1.      1.Reserved.

2.      2.Reserved.

3.      3.Reserved.

4.      4.Reserved.

5.      5.Reserved.

6.      6.Reserved.

7.      7.Reserved.

 

Note: Conveying systems such as platform Lifts, Stairway Chairlifts, Limited-use/Limited-Application Elevators may be used to provide vertical accessibility where the building is exempt from the ADA requirements for an elevator.

Advisory 206.2.3 Multi-Story Buildings and Facilities. Spaces and elements located on a level not required to be served by an accessible route must fully comply with this code. While a mezzanine may be a change in level, it is not a story. If an accessible route is required to connect stories within a building or facility, the accessible route must serve all mezzanines.

Advisory 206.2.3 Multi-Story Buildings and Facilities Exceptions.
Exceptions 1 – 7 are preempted by Florida vertical accessibility requirements of s.553.509, F.S., as incorporated in section 201.1.1. Florida requirements may be waived down to the ADA Standards requirements.

Note: The following Advisories on the Exceptions to 206.2.3 are provided for consideration when waiving Florida Vertical Accessibility requirements down to ADA Standards for Accessible Design.

Advisory 206.2.3 Multi-Story Buildings and Facilities Exception 1. Note that Exception 1 as presented in the 2004 ADAAG must also comply with the elevator exemption criteria of 28 CFR 36.401(d). The elevator exemption is authorized by 28 CFR 36.401(d) and applies only to private entities governed by Title III but not to public entities governed by Title II and 28 CFR, Part 35. Note also that 28 CFR 36.401(d)(2) and (3) provide specific criteria expanding on the criteria of Exception 1 that must be considered in a waiver of Florida vertical accessibility.

Advisory 206.2.3 Multi-Story Buildings and Facilities Exception 2. Note that Exception 2 for a required accessible route applies to public entities, is not modified by 28 CFR, Part 35 and parallels the exception for vertical accessibility in s.553.509(1)(c), F.S., and 201.1.1(3).

Advisory 206.2.3 Multi-Story Buildings and Facilities Exception 4. Where common use areas are provided for the use of residents, it is presumed that all such common use areas “serve” accessible dwelling units unless use is restricted to residents occupying certain dwelling units. For example, if all residents are permitted to use all laundry rooms, then all laundry rooms “serve” accessible dwelling units. However, if the laundry room on the first floor is restricted to use by residents on the first floor, and the second floor laundry room is for use by occupants of the second floor, then first floor accessible units are “served” only by laundry rooms on the first floor. In this example, an accessible route is not required to the second floor provided that all accessible units and all common use areas serving them are on the first floor.

408 LIMITED-USE / LIMITED-APPLICATION ELEVATORS 408.1 General.

Limited-use/limited-application elevators shall comply with 408 and with ASME A17.1 (incorporated by reference, see “Referenced Standards” in Chapter 1).They shall be passenger elevators as classified by ASME A17.1. Elevator operation shall be automatic.

CHAPTER 4: ACCESSIBLE ROUTES SECTION 410 PLATFORM LIFTS

410.1 General.   Platform lifts shall comply with ASME A18.1 (1999 edition or 2003 edition) (incorporated by reference, see “Referenced Standards” in Chapter 1). Platform lifts shall not be attendantoperated and shall provide unassisted entry and exit from the lift.  

410.2 Floor Surfaces.   Floor surfaces in platform lifts shall comply with 302 and 303.  

410.3 Clear Floor Space.   Clear floor space in platform lifts shall comply with 305.  

410.4 Platform to Runway Clearance.   The clearance between the platform sill and the edge of any runway landing shall be 1 inch (32 mm) maximum.  

410.5 Operable Parts.   Controls for platform lifts shall comply with 309.  

410.6 Doors and Gates.   Platform lifts shall have lowenergy poweroperated doors or gates complying with 404.3. Doors shall remain open for 20 seconds minimum. End doors and gates shall provide a clear width 32 inches (815 mm) minimum. Side doors and gates shall provide a clear width 42 inches (1065 mm) minimum.   EXCEPTION: Platform lifts serving two landings maximum and having doors or gates on opposite sides shall be permitted to have selfclosing manual doors or gates.  

DS 2016-098. Petitioner seeks a Declaratory Statement on an interpretation of Chapter2, Section 206.7 – 206.7.5 and Chapter 4, Section 410 – 410.6 of the Florida Building Code, Accessibility – 5th Edition (2014)

Questions:

 

As opposed to seeking a waiver to install a platform lift in this situation, is the use of a platform lift acceptable in accordance with FBC 2014-Accessibility sections 410 and 206.7?  Should a waiver be required for a design that apparently meets code requirements?

 

 

Answer: To question “is the use of a platform lift acceptable in accordance with FBC 2014Accessibility sections 410 and 206.7?” The answer is yes. A platform lift that is incompliance with Sections 410 and 206.7 and listed/certified for the intended use is acceptable for the project in question.

 

To question “should a waiver be required for a design that apparently meets code requirements?”   The answer is no.  A waiver application is not necessary for the project in question.  

 

Staff Analysis:

Question:

 

Does the Florida Accessibility Code - Sections 201.1.1 and 206.2.3 allow Limited­ Use / Limited Application Elevators or Platform Lifts installed per FAC 408 or 410 to meet the requirements for vertical accessibility in buildings where the ADA does not require vertical accessibility?

Answer:

Option #1/Petitioner: Petitioner respectfully believes that the answer to the question outlined above is "Yes."

Option #2/Staff:  

The answer to the question is “Yes.” Limited-Use/Limited Application Elevators or Platform lifts installed as per Section 408 or 410 of the 6th Edition (2017) Florida Building Code, Accessibility and listed/certified for the intended use are acceptable for the project in question.